DIGITAL-SETPOINT UPPER BOARD OPTION 06 Form-C reed-relay output TTL output LED alarm indicator Latched or non-latched operation Front-panel RESET button Remote RESET APPLICABLE INSTRUMENTS Model 204B,2003B and 2004 for DC, AC, true-RMS or process signals Models 267B and 268 for thermocouple or RTD temperature signals The 06 is an upper-board option which adds a single setpoint for digital control or alarm to a host digital panel meter. Its outputs are one Form-C reed relay, one TTL output and one front-panel LED, which flashes when the meter reading is in the alarm zone. OPERATING MODES The 06 can be hardwired for latched or non-latched operation. In latched operation, the alarm outputs stay activated until reset by a front-panel reset pushbutton or momentarily grounding a pin on the rear connector. In non-latched (or automatic-reset) operation, the alarm outputs are only activated while the input to the meter is in the alarm zone. If the polarity pin is not connected, the 06 will alarm on the absolute value of a positive or negative signal. This allows operation as a null-band detector. PROGRAMMING The 06 is programmed by hardwiring selected BCD lines from the main board of the meter. When all of the selected BCD lines go true, the 06 senses an alarm condition. SPECIFICATIONS CONTROL/ALARM OUTPUTS Relay output: Form-C reed relay Contact rating: 5 W at 0.5 A or 200 V dc max, non-inductive load Contact resistance, max: 100 m Switching time: 1 ms (nominal) TTL output: 1 TTL unit load LED indicator: Flashes in alarm condition POWER Power: 5 V dc and 40 mA from host DPM ENVIRONMENTAL Operating temperature: 0 to 55°C Storage temperature: 40 to +85°C Relative humidity: 95% at 40°C (non-condensing) MECHANICAL Form factor: Newport DIN1A upper board Dimensions: 85 x 119 mm(3.35 x 4.69 in) D3 connector: 36-pin, double-row, solder-type HOME / PRODUCT GUIDE / TECHNICAL REFERENCE NEWPORT Electronics, Inc. (714) 540-4914 or Contact Us Copyright 1998, Newport Electronics, Inc. All rights reserved. |